The LRF300H (0.05–300 m at 90% reflectivity) and LRF600H (0.05–600 m) can both be commissioned for fixed-mount industrial distance measurement. The critical work is not in the sensor itself — it is in five preparation areas that determine whether the installation stays stable over its service life: alignment and target sizing, filtering and averaging, alarm configuration, enclosure and cable integrity, and a signed handover record. If you are still at the selection stage, the Level & AGV integration checklist covers power rail, interface and IP rating choices before this commissioning checklist applies.
Fixed-mount measurement tasks
A fixed-mount installation replaces a handheld survey with a permanently positioned module. The LRF300H and LRF600H stream distance data continuously at 1 kHz, or at 50 Hz when echo strength is low — the modules switch between these rates automatically to match the signal returned by the target. The 9–36 V DC supply and −20 to +60 °C operating range suit most industrial environments, from temperature-controlled factory bays to outdoor structures. Fixed mounting introduces two constraints that a handheld survey does not face: the alignment cannot be re-adjusted during production, and all reading instability — from echo loss, vibration, temperature drift or contamination — becomes a process fault rather than an operator decision. Each of the five sections below addresses one of these failure paths.
Alignment and target plate
The module field of view is approximately 4 mrad. At 50 m that corresponds to a beam spot roughly 0.2 m across; at 100 m approximately 0.4 m; at 300 m approximately 1.2 m; at 600 m approximately 2.4 m. The target surface must fully intercept the beam at the furthest intended measurement distance. If the target is smaller than the beam spot, part of the energy is lost, the signal budget is reduced and the auto-rate logic may hold the module at its lower 50 Hz output. Use a plate that approximates the material reflectivity expected during normal operation for the final acceptance measurement — a bright white panel verifies the optics; only a panel matching the actual target confirms the installation will work throughout the production range.
Mount the module perpendicular to the target surface. Any tilt increases the angle of incidence and reduces the returned signal compared to a normal-incidence measurement. Use the four M2 mounting holes on the 29 × 13.25 mm pattern on the lens face; screws should not project more than 5 mm into the housing. For LRF600H the factory has confirmed that M2 screws with a maximum insertion depth of 5 mm are correct. Apply thread-locking compound in vibration environments after final beam alignment is set.
Filtering, averaging and alarm settings
Both modules output a 4-byte little-endian frame with header byte 0x5C, two distance bytes and a check byte. When the module cannot obtain a valid echo, it outputs 65535 — the maximum value of the two-byte distance field, representing out-of-range at 65535 cm. Alarm logic in the host controller must treat 65535 as “no valid reading” rather than interpreting it as a distance value. This is the most common commissioning error on a fresh fixed-mount installation: the alarm threshold is set against a distance range that does not explicitly exclude 65535, so a brief loss of echo triggers a false distance alarm instead of a “no target” fault.
For a target that changes slowly — a tank level, a gap sensor, a crane stop — averaging 10 to 50 consecutive valid readings improves displayed stability without introducing significant lag. The LRF600H filter time constant adjusts how the module’s internal averaging responds as the update rate switches between 1 kHz and 50 Hz; see LRF600H: Keep Filter Timing Stable as Rate Changes for the parameter details. For receive-gap alarms — a supervisory function that triggers when valid readings are absent for a defined interval — see LRF600H: Set a Receive-Gap Alarm.
At distances near the 10%-reflectivity boundary (100 m for LRF300H, 200 m for LRF600H) expect the module to hold the lower 50 Hz rate on dark-surface targets. For the full treatment of how reflectivity affects range and rate, see Laser Rangefinder Accuracy: What ±1 m Means.
Window, enclosure and cable checks
The H-series modules do not publish an ingress-protection rating. For any outdoor, wash-down or dusty installation an external enclosure is required. If a protective window is part of the enclosure design, test its effect in three steps: measure the bare module in a stable fixture, then repeat with the window in its specified orientation, then repeat again with the full enclosure including bezel and seals. A window that passes the loose-piece test may still obstruct or reflect once the enclosure is closed. The methodology is covered in Rangefinder Protective Window Checklist.
The module ships with 50 cm stranded wires on a 1.25 mm 5-pin connector. For longer runs to a junction box or controller, verify that the total cable length is compatible with UART at 460800 baud. The LRF300H and LRF600H communicate over UART and I²C only; they do not carry native RS-485 or CAN. For runs beyond 3–5 m, include a UART-to-RS-485 converter module in the bill of materials from the start rather than discovering the gap during integration. For LRF600H, the factory has confirmed that TX and RX are 3.3 V logic, independent of the 9–36 V power supply; a 5 V UART host requires a level shifter. For LRF300H the signal level is not specified in the published datasheet; confirm with ERDI before wiring. See the 905 nm UART OEM module page for a summary of the electrical interface.
Commissioning and handover checklist
Record the following items before signing off a fixed-mount installation. Each blank entry is a commissioning gap, not a default: unknown values must be measured or confirmed with the supplier before the system is handed over.
- Module model and serial number — read from the module via the “Reading serial no.” command, which returns the S-prefixed serial number stored in the module.
- Supply voltage at module terminals — measure the DC voltage; confirm it is within 9–36 V under load.
- Target surface description — material, colour, angle of incidence and approximate reflectivity.
- Working distance and range margin — confirm the installed distance is below the 10%-reflectivity range limit for the material in use (100 m for LRF300H, 200 m for LRF600H).
- Observed update rate — record whether the module is operating at 1 kHz or 50 Hz at the working distance and target.
- Out-of-range value handling confirmed — verify in the host logic that a 65535 output is treated as “no valid reading” and not as a distance value.
- Averaging and filter settings — number of samples averaged; filter time constant if set on LRF600H.
- Alarm thresholds set — distance alarm limits and receive-gap alarm window, with 65535 excluded from the distance range check.
- Window and enclosure fitted and tested — window drawing reference, three-step acceptance test completed, IP enclosure confirmed.
- Cable run length and interface — total UART cable length; converter model if RS-485 is used; signal level confirmed for the host UART.
- Mounting screws torqued and locked — M2 screws with insertion depth ≤5 mm; thread-lock applied if vibration is present.
- Environmental conditions at sign-off — ambient temperature, ambient light level, any condensation or contamination noted.
FAQ
How do I align a fixed-mount rangefinder to its target?
Mount the module so the lens face is perpendicular to the target surface. Use the four M2 holes on the 29 × 13.25 mm pattern with screws that project no more than 5 mm into the housing. With the module powered and streaming, monitor the valid-reading rate in real time while making small angular adjustments; a sharp increase in valid readings and a stable distance value indicate correct alignment. Secure screws with thread-lock compound before closing the enclosure. Repeat the valid-reading check through any window or enclosure glass that is added afterward.
Should I average readings on a fixed installation?
Yes, in most cases. For a target that changes slowly — a tank level, a crane stop position, a gap measurement — averaging 10 to 50 consecutive valid readings reduces display jitter without meaningful lag. Discard the 65535 out-of-range value before computing the average; including it will produce incorrect results. If the target moves quickly, reduce the sample window or disable averaging so the controller sees changes promptly. For LRF600H the filter time constant also affects how the internal averaging responds when the update rate switches between 1 kHz and 50 Hz.
What should be recorded at handover?
Record the module serial number, the measured supply voltage, the target description and working distance, the observed update rate (1 kHz or 50 Hz), confirmation that 65535 is handled as “no valid reading” in the host logic, the alarm threshold values, the window and enclosure details including the three-step acceptance test, the cable run length and interface type, the mounting screw depth and locking method, and the environmental conditions at sign-off. These 12 items make up the minimum handover record described in this article.
For model selection guidance before installation, see the 905 nm UART OEM module overview. To confirm the right model for a specific working distance, target material, enclosure design and host interface, contact ERDILRF with your requirements for a written recommendation.